Check valve (one-way valve): allows refrigerant flow only in one direction, prevents reverse flow when pressure reverses. Typical application: hot gas defrost return line, parallel compressor discharge manifold, avoid high pressure gas backflow. Spring check valve is used for refrigeration system; low cracking pressure type for low flow circuit. Ball valve: full bore, small flow resistance, used as maintenance isolation valve, for refrigerant circuit cut-off during overhaul. Globe valve: fine throttling capability, big flow resistance, used for manual balance adjustment of oil return or hot gas branch. Xiteliduo rack system configures ball valve at inlet/outlet of each circuit for convenient single-circuit maintenance. Check valve cannot be installed horizontally in some low-temperature oil circuit; wrong orientation leads to oil accumulation. Ball valve is not designed for flow regulation; long-term half-open position will damage sealing ball seat. All refrigeration valves must match refrigerant and pressure grade; ordinary water valve cannot replace refrigeration dedicated valve. Refrigeration maintenance & repair company uses ball valve to isolate faulty circuit, keep other cold room circuits running.