Refrigeration machine room concentrates compressor rack, receiver, control cabinet; layout determines safety, maintenance and stability. Core layout rules: reserved maintenance space around each unit, clear access channel, separate electrical area and refrigerant vessel area. Machine room heat load comes from compressor power loss, condenser heat radiation, electrical cabinet heat; ventilation must remove surplus heat. Air cooled condenser is often placed outdoor; if installed inside machine room, strong forced ventilation is mandatory to avoid hot accumulation. Refrigerant safety zoning: natural refrigerant such as CO₂ requires gas detector and forced exhaust fan interlock. Fire separation: machine room separate from cold storage and office; fire door, fire barrier comply with local building code. Pipeline arrangement: suction line at upper layer, liquid line middle, drain and cable at lower layer; label each circuit clearly. Control cabinet position: avoid direct radiation from compressor and condenser, reduce high temperature impact on electric components. Emergency facilities: emergency stop button, gas alarm, exhaust fan, eye wash station required for some export standards. Refrigeration maintenance & repair company reserves lifting space for compressor replacement in machine room early in design.